Parameters |
AC 800V-2*5MW |
Rated Voltage |
AC 800V/50HZ,3-phase 4-wire |
Max Rated Power |
2X5MW |
Load steps |
Total 10MW:combine with 2 sets of 5MW .
10KW+2*20KW+50KW+2*100KW+200KW+9X500KW
Note :
1.arbitrarily combined with the following load steps, 3-phase synchronization |
Load test accuracy |
≤±5% |
Sampling accuracy |
0.5 class |
Display accuracy |
0.5%F.S |
Power factor |
PF=1.0 |
Display mode |
Voltage /Current/Power/Frequency |
Work power |
AC400V/50HZ,3-phase 4-wire(FAN Power supply) |
Wire connection |
Copper (L1,L2,L3) |
Work Mode |
Continuous work |
Cooling Mode |
Force-air cooling. Air take from side, out from top,with air duct. |
Control mode |
1. Local Manual Control with Button and Contactor
2. Remote control with RS485,and with 20 meters long remote control wire . |
Over-voltage protection |
When input voltage exceeds the safety threshold, it will automatically unload and alarm. |
Over-current protection |
Automatically unload and protect when there is a over-current in the main circuit |
Over-temperature protection |
When temperature exceeds the safety threshold, it will automatically unload and alarm. |
Fan fault protection |
when any fan fails to operate normally, it will automatically unload and alarm. |
Fan power phase sequence protection |
When fan power phase sequence is wrong, fan can’t be started and load can’t power on. |
Emergency stop |
Manually unloaded , and it cannot be loaded in the state of emergency stop lock. |
Color |
Grey |
Move mode |
Forklift and Lifting rings for easy lifting. |
Ambient Temperature |
-10℃~+50℃ |
Humidity |
≤95% |
Other conditions |
For outdoor use(Whole part IP54) with Air duct. |
Demension(About) |
Per Cabinet: W2438*H2438*D11000 ,total 2 cabinet
10 PCS Air Duct:W1300*H1000*L1400 (subject to actual) |
Weight |
About 12~17t (subject to actual) |